MAINTENANCE INSTRUCTIONS FOR POWER TRANSFORMERS
Check colour of active agent If silicagel is pink, change by new charge. 10 Daily Relief diaphragm of OLTC explosion vent Replace if cracked or broken 11 Daily Cooler fan, bearing motor operating mechanism Check the bearings. Examine contacts, check manual control and interlock Lubricate the bearing.